csiweb > grease ducts > schebler grease duct

Schebler
Grease Duct
CSI CONSERVATION SYSTEMS INC 407.351.9121    CONTACT    BACK    HOME
   
Factory-Built Multi-Wall Grease Duct
  • Heavy duty multi-wall design reduces skin temperatures, decreasing combustible clearance requirements and transferring less heat to the surrounding environment.
  • Light-weight easy-to-handle lengths can be assembled and installed easily by one person without using special tools thus lowering field installation costs.
  • All fittings are laser cut to exacting UL standards and all welding is done at the factory. Each individual piece is rigorously tested for material integrity, structural stability, and skin temperature.
  • All four models feature double-wall construction: Model PA has a 1" air space between the shell and liner; Models P1, P2A and P4 combine air spaces with the added benefit of high density ceramic fiber insulation.

Shebler Grease Ducts are assembled on site without welding from light-weight, easy-to-handle prefabricated components.

Return to Top of Page
   
Grease Duct Models
Model PA
High performance standard product with a 1" air space between the shell and liner. Suitable for most grease duct applications.


Click to enlarge.

Model P2A
Extra heavy duty duct with 3" air space filled with 2" of high-density ceramic fiber insulation and a 1" air gap. Compared to Model PA, cold face temperature can be reduced by an additional 50%.

Model P2A: Double-Wall; 2" Insulation
Click to enlarge.

   
Model P1
Heavy duty duct with 1" blanket of ceramic fiber insulation between the shell and liner that can lower the cold face temperature by as much as 35%.

Model P1: Double-Wall; 1" Insulation
Click to enlarge.

Model P4
Super-insulated heavy duty duct with a 4" gap between the shell and liner filled with high-density ceramic fiber insulation. Cold-face temperature can be as much as 67% lower than the Model PA.

Model P4: Double-Wall; 4" Air Gap/Insulation
Click to enlarge.

Return to Top of Page
   
Components
Components available in even and odd diameters ranging from 6" to 48" (larger diameters available upon request up to 60" diameter and larger).
Standard components include: Straight Sections, Adjustable Lengths, Expansion Joints, Tee's, Elbows, Wyes, Drain Sections and Tees, Increasers, Rain Caps, Roof Penetrations, guides and support members. In addition, virtually any conceivable fitting is available as a special order item.
Standard ducts feature a Type 304 stainless steel liner (sufficient for most applications) and an aluminized steel outer shell. For increased resistance to the corrosive effects of combustion byproducts, Type 316 stainless steel is available for the liner and either Type 304 or 316 stainless steel steel for the shell. For exterior sections that are not easily accessible for periodic painting, a Type 304 stainless steel outer shell requires no maintenance.
Standard liners are 20 gauge steel; standard shells are 22 gauge aluminized steel. Fittings larger than 24" Ø feature 18 guage steel; pipe larger than 36" Ø uses only 18 gauge steel.
All Schebler components are subjected to structural tests, wind load tests, and skin temperature tests.
Listed by Underwriters Laboratories, Inc. (UL) under file MH17739 for use in Grease Duct applications to 500°F (260°F) continuous and 2000°F (1093°C) intermittent. [UL Listing 1978]
Return to Top of Page
   
Clearances
PA & P1
Inside Diameter Clearance
5-6 6
8-12 8
14-16 10
18-20 11
22-24 12
26-28 14
30-32 16
34-48 18

P2A & P4

Inside Diameter Clearance
5-6 2
8-12 3
14-16 4
18-20 5
22-24 6
26-30 7
32-34 8
36-38 9
40-42 10
44-48 11
Return to Top of Page
   
Notes
These chimneys are to be installed as per the Schebler Co. installation instructions. They are not to be enclosed within combustible construction. An unenclosed chimney may be placed adjacent to walls of combustible construction at the clearances specified.
All systems ship with S2000 UL Listed sealant. Sealant must be used for all applications where the flue temperature will be over 600°F and up to 2000°F.
Standard warranty is for one (1) year from date of system startup; warranty is extended to 10 years for Schebler-designed systems; contact Schebler at 563.359.0110.
CSI does not stock this item; it is available only F.O.B. Bettendorf, Iowa; lead times vary; call us at 407.351.9121 for more information or call The Schebler Company at 563.359.0110 or visit them at www.schebler.com.
Return to Top of Page
  
Central Florida Representative:
Manufacturer:
Conservation Systems, Inc.
5850 Lakehurst Drive, Suite 120
Orlando, FL 32819-8386
407.351.9121 Phone
407.352.6391 Fax
www.csiworldwide.com
The Schebler Company
Chimney Division
5665 Fenno Road
Bettendorf, Iowa 52722-5711
(319) 359-0110 Phone
(319) 359-8430 Fax
www.schebler.com
 
Specifications subject to change without notice.
Please read our Terms of Sale notice carefully before placing an order.
Site Copyright 2006 © Conservation Systems, Inc. Orlando, Florida USA
All other trademarks, logos and copyrights are the property of their respective owners.
Return to Top of Page